§ 30-41. Access to concealed spaces.
Latest version.
-
A.All concealed or closed-off spaces above ceilings or other similar areas shall be provided with suitable access from either the interior or exterior of the structure whenever said spaces contain any fire-detecting equipment or devices, fire-suppression equipment or devices or smoke/fire-control equipment or devices. This section does not apply to spaces that contain only wiring or piping for such equipment or devices.B.Access opening required by this section shall have a minimum clear opening of not less than 24 inches by 48 inches.C.One access opening shall be provided for each 3,000 square feet of concealed or closed-off space.D.Access opening shall be arranged so that the maximum travel distance from any opening to the farthest area of such concealed or closed-off space does not exceed 75 feet.E.Every access opening shall have the same fire resistance rating as the wall/ceiling/floor assembly in which it is located.
Amended 12-20-1988 by L.L. No. 30-1988, effective 12-27-1988