§ 30-182. Compliance inspection.  


Latest version.
  • A. 
    Once the installation or modification of a carbon monoxide detection system, combination carbon monoxide detection system or combination system has been completed in accordance with the approved permit submission and verified by the installer to be in full operating condition, the installer shall contact the Division of Fire Prevention to schedule a certificate of compliance inspection.
    B. 
    A certificate of compliance inspection shall be conducted in the presence of a Fire Marshal from the Division of Fire Prevention, during which the following shall be witnessed and/or verified:
    (1) 
    Testing of all systems/detection devices shall be performed by the introduction of carbon monoxide into the sensing chamber or element. Test/Activation by other means, such as magnets, is not acceptable.
    (2) 
    The result of each carbon monoxide detector test shall be confirmed through indication at the detector and the control panel.
    (3) 
    The operation of all occupant notification devices shall be witnessed.
    (4) 
    Circuit supervision, "Trouble," "Supervisory" and "Alarm" conditions, shall be witnessed.
    (5) 
    Receipt of alarm at central station or supervising station shall be verified.
    C. 
    A certificate of completion shall be submitted to the Fire Marshal upon completion of the inspection.